10kV dry-type transformer
10kV dry-type transformers are suitable for installation in places with limited space, close to the load center, requiring fire prevention and explosion prevention, such as urban central areas, residential areas, hospitals, schools, hotels, high-rise buildings, commercial centers, transportation hubs, industrial parks, petrochemical plants, offshore drilling floors and other places where oil-immersed transformers are not suitable.
Safe and reliable
Well-made
After-sales worry-free
Quality Assurance
Classification:
6kV-35kV dry-type transformer
Telephone:86-371-63719330
Product Introduction
10kV dry-type transformers are suitable for installation in places with limited space, close to the load center, requiring fire prevention and explosion prevention, such as urban central areas, residential areas, hospitals, schools, hotels, high-rise buildings, commercial centers, transportation hubs, industrial parks, petrochemical plants, offshore drilling floors and other places where oil-immersed transformers are not suitable.
Compared with group a performance index of GB/T10228-2008 "technical parameters and requirements for dry-type power transformers", type 13 products have no-load loss reduced by 40%, load loss reduced by 15%, and the comprehensive cost is extremely low.
Compared with group a performance index of GB/T10228-2008 "technical parameters and requirements for dry-type power transformers", type 11 products have no-load loss decreased by 30%, load loss decreased by 5%, and comprehensive cost is low.
Transformer inlet and outlet modes
Both sides of the high and low voltage transformer can adopt the upper or lower line inlet mode. The top of the shell has reserved line inlet. For the lower line, the shell is equipped with a cable card to fix the incoming cable.
The low voltage transformer can also provide standard enclosed bus, standard horizontal side outgoing line and standard vertical side outgoing line (to be customized).
10kV class dry-type transformer appearance drawing
Parameters of SCB10-30 ~ 2500 Epoxy Resin Casting Dry-type Transformer
Model |
11 |
Voltage combination and tap range |
|
Join Group Label symbol |
short circuit impedance |
No-load loss |
Load loss Load |
No-load current |
SC10-30 |
±5% |
0.38 0.415 0.433 |
YynO |
4% |
0.19 |
0.71 |
2.1 |
|
SC10-50 |
0.27 |
1.00 |
2.1 |
|||||
SC10-80 |
0.37 |
1.38 |
1.6 |
|||||
SC10-100 |
0.4 |
1.57 |
1.6 |
|||||
SC10-125 |
0.47 |
1.85 |
1.5 |
|||||
SC10-160 |
0.54 |
2.13 |
1.5 |
|||||
SC10-200 |
0.62 |
2.53 |
1.3 |
|||||
SC10-250 |
0.72 |
2.76 |
1.3 |
|||||
SC(B)10-315 |
0.80 |
3.47 |
1.1 |
|||||
SC(B)10-400 |
0.98 |
3.99 |
1.1 |
|||||
SC(B)10-500 |
1.16 |
4.88 |
1.1 |
|||||
SC(B)10-630 |
6% |
1.3 |
5.96 |
0.9 |
||||
SC(B)10-800 |
1.52 |
6.96 |
0.9 |
|||||
SC(B)10-1000 |
1.77 |
8.13 |
0.9 |
|||||
SC(B)10-1250 |
2.09 |
9.69 |
0.9 |
|||||
SC(B)10-1600 |
2.45 |
11.73 |
0.9 |
|||||
SC(B)10-2000 |
3.05 |
14.45 |
0.9 |
|||||
SC(B)10-2500 |
3.6 |
17.17 |
0.7 |
Parameters of SCB11-30 ~ 2500 Epoxy Resin Casting Dry-type Transformer
Model |
Voltage combination and tap range |
Join Group Label |
short circuit impedance |
No-load loss |
Load loss |
No-load current No-load current |
||
High pressure |
High voltage tap range |
Low pressure |
||||||
SC11-30 |
11 |
±5% |
0.38 |
Yyn0 |
4% |
0.17 |
0.71 |
1.9 |
SC11-50 |
0.24 |
1.00 |
1.9 |
|||||
SC11-80 |
0.33 |
1.38 |
1.5 |
|||||
SC11-100 |
0.36 |
1.57 |
1.5 |
|||||
SC11-125 |
0.42 |
1.85 |
1.3 |
|||||
SC11-160 |
0.48 |
2.13 |
1.3 |
|||||
SC11-200 |
0.55 |
2.53 |
1.1 |
|||||
SC11-250 |
0.64 |
2.76 |
1.1 |
|||||
SC(B)11-315 |
0.79 |
3.47 |
1.0 |
|||||
SC(B)11-400 |
0.88 |
3.99 |
1.0 |
|||||
SC(B)11-500 |
1.04 |
4.88 |
0.9 |
|||||
SC(B)11-630 |
6% |
1.17 |
5.96 |
0.9 |
||||
SC(B)11-800 |
1.36 |
6.96 |
0.9 |
|||||
SC(B)11-1000 |
1.59 |
8.13 |
0.9 |
|||||
SC(B)11-1250 |
1.88 |
9.69 |
0.9 |
|||||
SC(B)11-1600 |
2.2 |
11.73 |
0.7 |
|||||
SC(B)11-2000 |
2.74 |
14.45 |
0.6 |
|||||
SC(B)11-250C |
3.24 |
17.17 |
0.6 |
Parameters of SCB12-30 ~ 2500 Epoxy Resin Casting Dry-type Transformer
Model |
|
Voltage combination and tap range High voltage tap range Tapping range |
|
Join Group Label |
short circuit impedance |
No-load loss loSS |
Load loss |
No-load current |
SC12-30 |
11 |
+5% |
0.38 |
Yyn0 |
4% |
0.15 |
0.71 |
2.4 |
SC12-50 |
0.215 |
1.00 |
2.4 |
|||||
SC12-80 |
0.295 |
1.38 |
1.8 |
|||||
SC12-100 |
0.32 |
1.57 |
1.8 |
|||||
SC12-125 |
0.375 |
1.85 |
1.6 |
|||||
SC12-160 |
0.43 |
2.13 |
1.6 |
|||||
SC12-200 |
0.495 |
2.53 |
1.4 |
|||||
SC12-250 |
0.575 |
2.76 |
1.4 |
|||||
SC(B)12-315 |
0.705 |
3.47 |
1.2 |
|||||
SC(B)12-400 |
0.785 |
3.99 |
1.2 |
|||||
SC(B)12-500 |
0.93 |
4.88 |
1.0 |
|||||
SC(B)12-630 |
6% |
1.04 |
5.96 |
1.0 |
||||
SC(B)12-800 |
1.215 |
6.96 |
1.0 |
|||||
SC(B)12-1000 |
1.415 |
8.13 |
1.0 |
|||||
SC(B)12-125C |
1.67 |
9.69 |
1.0 |
|||||
SC(B)12-1600 |
1.96 |
11.73 |
1.0 |
|||||
SC(B)12-2000 |
2.44 |
14.45 |
0.8 |
|||||
SC(B)12-2500 |
2.88 |
17.17 |
0.8 |
Parameters of SCB13-30 ~ 2500 Epoxy Resin Casting Dry-type Transformer
Model |
By pressure combination and tap range |
Join Group Label |
short circuit impedance |
No-load loss loss |
Load loss Load |
No-load current (%) |
||
High pressure |
High voltage tap range |
Low pressure |
||||||
SC13-30 |
11 |
±5% |
0.38 |
Yyn0 |
4% |
0.135 |
0.64 |
2.4 |
SC13-50 |
0.20 |
0.90 |
2.4 |
|||||
SC13-80 |
0.265 |
1.24 |
1.8 |
|||||
SC13-100 |
0.29 |
1.41 |
1.8 |
|||||
SC13-125 |
0.34 |
1.66 |
1.6 |
|||||
SC13-160 |
0.39 |
1.91 |
1.6 |
|||||
SC13-200 |
0.445 |
2.27 |
1.4 |
|||||
SC13-250 |
0.52 |
2.48 |
1.4 |
|||||
SC(B)13-315 |
0.635 |
3.12 |
1.2 |
|||||
SC(B)13-400 |
0.71 |
3.59 |
1.2 |
|||||
SC(B)13-500 |
0.835 |
4.39 |
1.0 |
|||||
SC(B)13-630 |
6% |
0.94 |
5.36 |
1.0 |
||||
SC(B)13-800 |
1.09 |
6..26 |
1.0 |
|||||
SC(B)13-100C |
1.27 |
7.31 |
1.0 |
|||||
SC(B)13-1250 |
1.50 |
8.72 |
1.0 |
|||||
SC(B)13-1600 |
1.76 |
10.50 |
1.0 |
|||||
SC(B)13-2000 |
2.19 |
13.00 |
0.8 |
|||||
SC(B)13-2500 |
2.59 |
15.40 |
0.8 |