YB pre-installed substation (European box substation)
+
  • YB pre-installed substation (European box substation)

YB pre-installed substation (European box substation)

European-style box-type substation, also known as European-style pre-installed substation or European-style combined substation, referred to as European-style box-type substation. It is a compact complete set of power distribution equipment that combines high-voltage switchgear, distribution transformers and low-voltage switchgear according to a certain wiring scheme. It is used in urban high-rise buildings, urban and rural buildings, luxury villas, square parks, residential quarters, industrial and mining enterprises and temporary power construction sites for receiving and distributing power in the power distribution system.

Safe and reliable

Well-made

After-sales worry-free

Quality Assurance

Classification:

Box-type substation

Telephone:86-371-63719330

Product Introduction

European-style box-type substation, also known as European-style pre-installed substation or European-style combined substation, referred to as European-style box-type substation. It is a compact complete set of power distribution equipment that combines high-voltage switchgear, distribution transformers and low-voltage switchgear according to a certain wiring scheme. It is used in urban high-rise buildings, urban and rural buildings, luxury villas, square parks, residential quarters, industrial and mining enterprises and temporary power construction sites for receiving and distributing power in the power distribution system.

YB pre-installed substation (European box substation) technical parameters

Item Objective L t e m

Unit

Reference Number  Data

 
High pressure sheet

Rated frequency Frequecy

Hz

50

Rated voltage Voltage

kV

1035

Maximum operating voltage Max Working Voltage

kV

6.911.540.5

工频耐受电压Industrial Requency Voltage-resisting
Ground and interphase /isolation fracture

kV

32/3642/4895/118

Lightning impulse withstand voltage Thundorand Lighting Ballistio
Ground and interphase /isolation fracture

kV

60/7075/85185/215

Rated current Current

A

400630

Rated short-time withstand current Rated ehort-time w ithetand current

kA

12.5(2S)16(2S)

Rated Crest Value Current-resisting

kA

32.54050

 
Low voltage unit

Rated voltage Voltage

V

380220

Rated Current Of Major Return Circuit

A

100-320

Rated short-time withstand current withstand current

kA

153050

Rated Crest Value Current-resisting

kA

3063110

Branch current Circuit

A

10-800

Branch Loop Number Quantity Of Branch

Road

12 January

Quantity

KVAR

0-360

 
Transformer Unit

Rated capacity Capacity

KVA

50-2000

短路阻抗Short-circuit Impedance

%

46

分接范围Scope Of Branch Connection

 

± 2 × 2.5%

Join Group Vector Group

 

Yyn0 Dyn11

Key words:

YB pre-installed substation

Related Products

Related Products

Product Consulting